Under NDA
NHS · sterile services
In-cabinet active suppression
NHS sterilisation unit: two fires, two outcomes
A bank of six machines on the 4th floor of an NHS hospital sterilises medical instruments at very high temperature, a service patient care depends on. A fire broke out inside one machine.
7 months
between the two fires
12 min
for the fire service to arrive, with no fire left to fight
2 days
to re-arm the system and resume service

Fire 1 · unprotected
Irreparable damage
- Staff tried portable extinguishers, without success
- The fire service put the fire out, but too late to save the machine
- Firefighting water spread far beyond the room
- Affected areas needed a full sterile clean and redecoration
- Critical patient care was seriously disrupted
The FirePro solution
Engineered in-cabinet
- FirePro identified motors and solenoids as the ignition sources
- Local FirePro control module
- 24 V DC power supply with standby batteries
- Linear heat detection inside the machine
- Two FirePro condensed aerosol generators
Fire 2 · protected
No smoke. No water. No fire.
- Suppression released inside the machine
- Machine power supply shut off
- Local fire doors closed and air handling stopped
- Ventilation dampers closed
- Fire alarm and BMS signalled




The same FirePro condensed aerosol technology protects our fire suppression charging lockers.

